2464 Multi Core Wires

Wires

About 2464 Multi Core Wire

Special Features

  • STYLE 2464 : Multi-conductor cable using Extruded Non-integral Jacket.
  • RATING : 80 deg C, 300 Vac, Cable flame.
  • INSULATED CONDUCTOR : Labeled or complying with manufacturer's AWM Procedure.
  • CONDUCTOR : 20 AWG - 2 AWG
  • ASSEMBLY : Two or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
  • COVERING : Optional
  • SHIELD : Optional
  • JACKET : Extruded PVC
  • COVERING : Optional, braid.
  • STANDARD : Appliance Wiring Material UL 758.
  • USE : Internal wiring or external interconnection of electronic equipment.
Diameter of cable under jacket Minimum average thickness Minimum thickness at any point
0.700 inch or less 30 mils 24 mils
0.701-1.000 inch 45 mils 36 mils
1.001-1.500 inch 60 mils 48 mils
1.501-2.500 inch 80 mils 64 mils
2.501-4.000 inch 110 mils 88 mils
4.001 inch and larger 140 mils 112 mils